モーリレー動作条件を考慮した電圧安定性ATC計算の提案

電気・情報関連学会中国支部連合大会講演論文集 Volume 58 Page 427-428 published_at 2007-10
アクセス数 : 1034
ダウンロード数 : 404

今月のアクセス数 : 6
今月のダウンロード数 : 12
File
rentai2007_p427_1204-1.pdf 285 KB 種類 : fulltext
Title ( jpn )
モーリレー動作条件を考慮した電圧安定性ATC計算の提案
Creator
Suenari Hiroyasu
Kawamoto Akinobu
Li Shenghu
Source Title
電気・情報関連学会中国支部連合大会講演論文集
Volume 58
Start Page 427
End Page 428
Abstract
This paper proposes a new computation method for Available Transfer Capability (ATC) with respect to voltage stability. In this paper, ATC is formulated as an optimization problem and solved by The Primal-Dual Interior Point Method (PDIPM). In stressed power system, it is possible that apparent impedance of mho relay falls in protection region and non-fault lines are tripped, which further stress the system and followed by cascading events. We considered this phenomenon in a computation method for ATC. In order to consider mho relay characteristics, we add mho relay operating conditions to the optimization problem as limits. The effectiveness of the proposed method is demonstrated through IEEE 30 bus systems.